Pressure Independent Zone Dampers

Pressure Independent operation is only available for round zone dampers. Use the chart
below to set the calibration of the zone damper after installation.

Damper

Size

Flow Probe

“K” Factor

6” 474
8” 950

10” 1417
12” 2120
14” 2908
16” 3700

Flow Probe “K” Factor =

CFM @ 1” Velocity Pressure

Table 1-3: Pressure Independent Flow Factors


Note: K Factors are programmed for each zone so that the correct CFM will be

calculated for the different size air valves.