Section 3

Auto-Zone Basic

3-22 Programming

Configuration Screen #5


Configuration Screen #6





Configuration Screen #7






The Zone Manager Bypass Damper normally opens in a
clockwise direction. If your bypass damper opens in a counter-
clockwise direction, select reverse acting instead of direct
acting
operation. To toggle between the two modes, press the
"*" key.

Bypass Act: Direct

PRESS (*) TO TOGGLE

The Zone Manager normally uses its own real-time clock and
an internal week schedule to determine the Occupied/
Unoccupied mode of operation. The Zone Manager does have
the ability to use a global broadcast from another scheduling
device on the communications loop if a more powerful schedule
is required. If an external schedule is used, the range of
schedule numbers is 1 to 8.

Zone Manager

Uses Schedule #: 0

0 = Internal Clock

1-8 = External Clock

Press (*) To Force

Recalibration Of The

Static Press. Sensor

<#> To Skip This...

The Zone Manager only calibrates the static pressure sensor
one time. That occurs on the initial powerup, so it is vital that
the sensor be attached before the system is ever powered up. If
you weren't able to do this or accidentally activated the system
before the sensor was available, you can force it to restart and
calibrate the static pressure sensor by pressing the "*" key. If
you don't need to re-calibrate, simply press the "#" key to skip
over this item.