Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 101: Vcc-x controller technical guide

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX D - VCC-X BACnet

®

101

VCC-X BACnet

®

Parameters

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Low Ambient

Protection

Setpoint

AV:36

Temperature at which the

Low Ambient Relay will

activate in the Occupied or

Unoccupied Mode.

-30

70

SAT Cool

Setpoint Reset

Source Low

Limit

AV: 37

If doing Supply Air Setpoint

Reset, this is the Low Reset

Source value in Cooling

that will correspond to the

Supply Air Cool High Reset

Setpoint.

-30

150

SAT Cool

Setpoint Reset

Source High

Limit

AV: 38

If doing Supply Air Setpoint

Reset, this is the High Reset

Source value in Cooling

that will correspond to the

Supply Air Cooling Setpoint

(Low Reset).

1

150

SAT Heat

Setpoint Reset

Source Low

Limit

AV: 39

If doing Supply Air Setpoint

Reset, this is the Low Reset

Source value in Heating that

will correspond to the

Supply Air Heating High

Reset Setpoint.

-30

150

SAT Heat

Setpoint Reset

Source High

Limit

AV: 40

If doing Supply Air Setpoint

Reset, this is the High Reset

Source value in Heating

that will correspond to the

Supply Air Heating Setpoint

(Low Reset).

1

150

Control

Temperature

High Alarm

Offset

AV:41

If the temperature of the

controlling sensor rises

above the Occupied Cooling

Setpoint by this value, a

High Control Temp Alarm

will occur. Only applies

if confi gured for Space or

Return Air Temp Control, or

as Single Zone VAV.

0

50

Control

Temperature

Low Alarm

Offset

AV:42

If the temperature of the

controlling sensor falls

below the Occupied Heating

Setpoint by this value, a

Low Control Temp Alarm

will occur. Only applies

if confi gured for Space or

Return Air Temp Control, or

as Single Zone VAV.

0

50

Heat Pump

Compressor

Heat Lockout

AV:43

Compressor Heat will

be locked out below this

setpoint.

-30

100

Maximum

Main Fan

VFD in Heat

Mode

AV:44

In Single Zone VAV

confi guration, this is the

max fan speed the VFD

can modulate up to in Heat

Mode.

0

100

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Minimum

Main Fan

VFD in

Cooling Mode

AV:45

In Single Zone VAV

confi guration, this is the fan

speed at which the VFD will

start when Cooling is

initiated. In a VAV

confi guration this is the

lowest fan speed allowed in

the Cooling Mode. In CAV

and MUA confi gurations

this should be set to 100%.

0

100

Minimum

Main Fan

VFD in

Heating Mode

AV:46

In Single Zone VAV

confi guration, this is the

fan speed at which the VFD

will start when Heating is

initiated. In a VAV

confi guration this is the

lowest fan speed allowed in

the Heating Mode. In CAV

and MUA confi gurations

this should be set to 100%.

0

100

Minimum

Main Fan

VFD in Vent

Mode

AV:47

Speed at which the VFD

will operate in the Vent

Mode in Single Zone VAV.

0

100

Maximum

Economizer in

Heating Mode

AV:48

Max position the

Economizer Damper can

open in the Heating Mode.

Takes priority over Max

Position in High CO2.

0

100

Minimum

Economizer

Position

AV:49

The minimum position of

the Outdoor Air damper in

the Occupied Mode. This

can be reset upwards based

on indoor CO2 levels.

0

100

Maximum

Economizer

CO2 Reset

Limit

AV:50

The maximum value the

Economizer

Minimum Position can be

reset up to

during CO2 override.

0

100

CO

2

Minimum

Setpoint

AV:51

This is the threshold CO

2

level at which the

Economizer Min Damper

Position Setpoint will begin

to be reset higher.

0

2000

CO

2

Maxi-

mum

Setpoint

AV:52

This is the CO

2

level at

which the Economizer Min

Damper Position will be re-

set to the Economizer Max

Position in High CO

2

. In

between the Min and Max

CO

2

levels the Economizer

Min Damper Position will

be proportionally reset

between the confi gured Min

Damper Position and the

Max Position in High CO

2

.

0

2000