Appendix a - system configurations, Head pressure transducer troubleshooting, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual

Page 81

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX A - SYSTEM CONFIGURATIONS

81

Head Pressure Transducer Troubleshooting

Table 10: Head Pressure Transducer Chart

Head Pressure Transducer

Troubleshooting

If you suspect there is a problem related to head pressure transducer
measurements, reference Table 10 below.

Head Pressure Transducer Chart

Voltage Pressure Voltage Pressure

0.5

0

2.6

350

0.6

17

2.7

367

0.7

33

2.8

384

0.8 50

2.9

400

0.9 67

3.0

417

1.0 83

3.1

434

1.1

100

3.2

450

1.2

117

3.3

467

1.3

133

3.4

484

1.4

150

3.5

500

1.5

167

3.6

517

1.6

183

3.7

534

1.7

200

3.8

550

1.8

217

3.9

567

1.9

233

4.0

584

2.0

250

4.1

600

2.1

267

4.2

617

2.2

283

4.3

634

2.3

300

4.4

650

2.4

317

4.5

667

2.5

334

Advertising