Vcc-x expansion module 1 wiring, Vcc-x em1 economizer actuator feedback wiring, Vcc-x em1 expansion module – Orion System VCC-X Controller User Manual

Page 40: Vcc-x controller technical guide 40, Vcc-x em1 economizer actuator feedback, Title 24 economizer feedback

Advertising
background image

VCC-X EXPANSION MODULE 1 WIRING

VCC-X Controller Technical Guide

40

VCC-X EM1 Economizer Actuator Feedback Wiring

Figure 25: VCC-X EM1 Economizer Actuator Feedback Wiring

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure
to observe polarity will result in damage to one or more of the boards. Expansion Modules
must be wired in such a way that the expansion modules and the controller are always
powered together. Loss of power to the expansion module will cause the controller to
become inoperative until power is restored to the expansion module.

VCC-X EM1
Expansion Module

Connect To
Expansion Module(s)
(When Used)

Connect To

Controller

VCC-X

Size Transformer
For Correct Total
Load. VCC-X E 1
Module = 5 VA

M

T3

WattMaster Label

#L102196-A

Rev.: 1A

B

A

T1

T2

ECON FEEDBACK

GND

SIG 2

+5V

BIN 1

SIG 1

BIN 2

GND

BIN 3

GND

GND

E-BUS

CONNECT

E-BUS

CONNECT

24 VAC POWE

WARNING! POL

MUST BE OBSE

THE CONTROLL

BE DAMAGED

POWER IN

BINARY INPUT TERMINALS

PRESSURE SENSOR INPUT

TERMINALS

TEMPERATURE SENSOR INPUT

TERMINALS

www.aaon.com

www.orioncontrols.com

O

NOT USED

Title 24 Economizer

Actuator Feedback

Signal 0-10VDC

(By Others)

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

+ 2

COM - 1

Economizer Feedback 5

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturer Wiring

Instructions

See Economizer
Actuator Wiring

For VCC-X

Controller

AO2

VCC-X EM1 Economizer Actuator

Feedback

The VCC-X EM1 Expansion Module (OE336-23-VCCXEM1)
connects to the VCC-X Controller with an EBC E-BUS cable and
adds an additional 5 Analog Inputs, 5 Analog Outputs, 3 Binary
Inputs, and 5 Confi gurable Relay Outputs.

The VCC-X EM1 Expansion Module can be used in conjunction with
the E-BUS 12-Relay Expansion Module. The expansion modules
can be used individually or together to provide the required inputs
and outputs for your specifi c applications.

Title 24 Economizer Feedback

If the controller has been confi gured for Title 24 Economizer
operation, the Economizer Actuator Feedback signal will be wired
to the VCC-X EM1’s T3 input.

See Figure 25 below for wiring.