Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 105: Vcc-x controller technical guide

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX D - VCC-X BACnet

®

105

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Compressor

D2 Alarm

BI:60

Compressor D2 High

Pressure Alarm. Stops

Compressor.

Outside Coil

'D' Temp

Switch

BI:61

Outside Coil 'D' Temp

Switch for Defrost Mode

Module #4

Binary Input

#4

BI:62

Future use for Binary Input

#4

On Board

Relay 1

BI:63

Current Status of Main Fan

Relay #1 on Main Board

On Board

Relay 2

BI:64

Current Status of

Confi gurable Relay #2 on

Main Board

On Board

Relay 3

BI:65

Current Status of

Confi gurable Relay #3 on

Main Board

On Board

Relay 4

BI:66

Current Status of

Confi gurable Relay #4 on

Main Board

On Board

Relay 5

BI:67

Current Status of

Confi gurable Relay #5 on

Main Board

On Board

Relay 6

BI:68

Current Status of

Confi gurable Relay #6 on

Main Board

On Board

Relay 7

BI:69

Current Status of

Confi gurable Relay #7 on

Main Board

On Board

Relay 8

BI:70

Current Status of

Confi gurable Relay #8 on

Main Board

Expansion

Module Relay

1

BI:71

Current Status of

Confi gurable Relay #1 on

EM1 Board

Expansion

Module Relay

2

BI:72

Current Status of

Confi gurable Relay #2 on

EM1 Board

Expansion

Module Relay

3

BI:73

Current Status of

Confi gurable Relay #3 on

EM1 Board

Expansion

Module Relay

4

BI:74

Current Status of

Confi gurable Relay #4 on

EM1 Board

Expansion

Module Relay

5

BI:75

Current Status of

Confi gurable Relay #5 on

EM1 Board

12 Relay

Expansion

Relay 1

BI:76

Current Status of

Confi gurable Relay #1 on

12 Relay Board

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

12 Relay

Expansion

Relay 2

BI:77

Current Status of

Confi gurable Relay #2 on

12 Relay Board

12 Relay

Expansion

Relay 3

BI:78

Current Status of

Confi gurable Relay #3 on

12 Relay Board

12 Relay

Expansion

Relay 4

BI:79

Current Status of

Confi gurable Relay #4 on

12 Relay Board

12 Relay

Expansion

Relay 5

BI:80

Current Status of

Confi gurable Relay #5 on

12 Relay Board

12 Relay

Expansion

Relay 6

BI:81

Current Status of

Confi gurable Relay #6 on

12 Relay Board

12 Relay

Expansion

Relay 7

BI:82

Current Status of

Confi gurable Relay #7 on

12 Relay Board

12 Relay

Expansion

Relay 8

BI:83

Current Status of

Confi gurable Relay #8 on

12 Relay Board

12 Relay

Expansion

Relay 9

BI:84

Current Status of

Confi gurable Relay #9 on

12 Relay Board

12 Relay

Expansion

Relay 10

BI:85

Current Status of

Confi gurable Relay #10 on

12 Relay Board

12 Relay

Expansion

Relay 11

BI:86

Current Status of

Confi gurable Relay #11 on

12 Relay Board

12 Relay

Expansion

Relay 12

BI:87

Current Status of

Confi gurable Relay #12 on

12 Relay Board

Refrig Module

#1 Relay #1

BI:88

Current Status of

Compressor A1 Enable

Refrig Module

#1 Relay #2

BI:89

Current Status of

Compressor A2 Enable

Refrig Module

#1 Relay #3

BI:90

Current Status of A1/A2

Condenser Enable

Refrig Module

#1 Relay #4

BI:91

Current Status of A1/A2

Reversing Valve

Refrig Module

#2 Relay #1

BI:92

Current Status of

Compressor B1 Enable

Refrig Module

#2 Relay #2

BI:93

Current Status of

Compressor B2 Enable

Refrig Module

#2 Relay #3

BI:94

Current Status of B1/B2

Condenser Enable

Refrig Module

#2 Relay #4

BI:95

Current Status of B1/B2

Reversing Valve

Refrig Module

#3 Relay #1

BI:96

Current Status of

Compressor C1 Enable

Refrig Module

#3 Relay #2

BI:97

Current Status of

Compressor C2 Enable

Refrig Module

#3 Relay #3

BI:98

Current Status of C1/C2

Condenser Enable

VCC-X BACnet

®