Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 104: Vcc-x controller technical guide 104

Advertising
background image

APPENDIX D - VCC-X BACnet

®

VCC-X Controller Technical Guide

104

VCC-X BACnet

®

Parameters

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Bad or

Missing

Module #1

BI:38

Refrigeration Module #1 is

bad or missing.

Bad or

Missing

Module #2

BI:39

Refrigeration Module #2 is

bad or missing.

Bad or

Missing

Module #3

BI:40

Refrigeration Module #3 is

bad or missing.

Bad or

Missing

Module #4

BI:41

Refrigeration Module #4 is

bad or missing.

Bad or

Missing

Preheat

Module

BI:42

Preheater Module is bad or

missing.

Bad or

Missing

Reheat Board

BI: 43

The MHGR board is

confi gured but not detected.

Bad or

Missing

MODGAS

Board

BI: 44

The MODGAS board is

confi gured but not detected.

Bad or Miss-

ing EM1

Module

BI:45

EM1 Expansion Board is

bad or missing.

Bad or

Missing 12

Relay

Expansion

Board.

BI: 46

The 12 Relay Expansion

Board is confi gured but not

detected.

Compressor

A1 Safety

BI:47

Compressor A1 Not

Running. This RSM alarm
occurs when a compressor

relay is on, but there is not

24VAC at the Comp Status

input for the compressor.

Compressor

A2 Safety

BI:48

Compressor A2 Not

Running. This RSM alarm
occurs when a compressor

relay is on, but there is not

24VAC at the Comp Status

input for the compressor.

Outside Coil

'A' Temp

Switch

BI:49

Outside Coil 'A' Temp

Switch for Defrost Mode

Module #1

Binary Input

#4

BI:50

Future use for Binary Input

#4

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Compressor

B1 Alarm

BI:51

Compressor B1 Not

Running. This RSM alarm
occurs when a compressor

relay is on, but there is not

24VAC at the Comp Status

input for the compressor.

Compressor

B2 Alarm

BI:52

Compressor B2 Not

Running. This RSM alarm
occurs when a compressor

relay is on, but there is not

24VAC at the Comp Status

input for the compressor.

Outside Coil

'B' Temp

Switch

BI:53

Outside Coil 'B' Temp Switch

for Defrost Mode

Module #2

Binary Input

#4

BI:54

Future use for Binary Input

#4

Compressor

C1 Alarm

BI:55

Compressor C1 High

Pressure Alarm. Stops

Compressor.

Compressor

C2 Alarm

BI:56

Compressor C2 High

Pressure Alarm. Stops

Compressor.

Outside Coil

'C' Temp

Switch

BI:57

Outside Coil 'C' Temp

Switch for Defrost Mode

Module #3

Binary Input

#4

BI:58

Future use for Binary Input

#4

Compressor

D1 Alarm

BI:59

Compressor D1 High

Pressure Alarm. Stops

Compressor.