APPENDIX D - VCC-X BACnet

®

VCC-X Controller Technical Guide

96

VCC-X BACnet

®

Connection To MS/TP Network

Figure 41: VCC-X BACnet Connection to MS/TP Network

MS/TP Connection

To BACnet

®

SHLD

T -

R +

Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R

Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.

2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted
pair with shield. Use Belden #82760 or equivalent.

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA

VCC-X CONTROLLER

Programming Note:

See Page 84

Use Settings Menu In
LCD Display To Program
The BACnet Settings.

For Details.