Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 103: Vcc-x controller technical guide

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX D - VCC-X BACnet

®

103

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Reserved For

Bad RAT

Sensor

BI: 13

Not Currently Used.

Bad Outdoor

Air Sensor

BI: 14

Failure of the Outdoor Air

Temperature Sensor.

Bad Space

Temp Sensor

BI: 15

Failure of the Space

Temperature Sensor. If

Space is the controlling

sensor, the unit will shut

down.

Bad CO2

Sensor

BI: 16

Failure of the CO2 Sensor.

Bad Relief

Pressure

Sensor

BI:17

Alarm indicating missing

or failed Building Pressure

Sensor.

Bad Outdoor

Airfl ow

Sensor

BI: 18

An Outdoor Airfl ow

Sensor is confi gured, but

not detected.

Bad Exhaust

Airfl ow Sen-

sor

BI: 19

An Exhaust Airfl ow

Sensor is confi gured, but

not detected.

Bad Supply

Airfl ow Sen-

sor

BI: 20

A Supply Airfl ow Sensor is

confi gured, but not detected.

Bad Return

Airfl ow Sen-

sor

BI: 21

A Return Airfl ow

Sensor is confi gured, but

not detected.

Mechanical

Cooling

Alarm

BI: 22

Compressor Relays are

enabled but the Supply Air
Temperature has not fallen

5°F w/in a user-adjustable

time period. This does

not apply for Modulating

Cooling.

Mechanical

Heating Alarm

BI: 23

Heating Mode has been

initiated but the Supply Air

Temperature has not risen

5°F w/in a user-adjustable

time period. This does

not apply for Modulating

Heating.

Fan

Proving Alarm

BI: 24

Alarm that indicates an

Airfl ow failure from the

Main Fan. Heating and

Cooling will be disabled.

Dirty Filter

Alarm

BI: 25

Alarm that indicates

the fi lters are dirty.

Emergency

Shutdown

Alarm

BI: 26

Alarm that indicates

that Emergency Shutdown

has been activated. Will

shut the unit down.

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Relay

Runtime
Warning

BI:27

Indicates when any of the
confi gured relays exceeds

a confi gured number of

hours of runtime. Can be
used to schedule service,

etc.

Economizer

Missing

BI:28

Title 24 operation indicates

missing economizer

feedback.

Economizer

Failure A

BI:29

Title 24 Air Temperature

Sensor Failure.

Economizer

Failure B

BI:30

Title 24 Not Economizing

when it should.

Economizer

Failure C

BI:31

Title 24 Economizing when

it should not.

Economizer

Failure D

BI:32

Title 24 Damper Not

Modulating.

Economizer

Failure E

BI:33

Title 24 Excess Outdoor Air.

High Supply
Temp Cutoff

Alarm

BI: 34

The Supply Air has risen
above the Hi SAT Cutoff

Setpoint. Heating stages

begin to deactivate and the

fan continues to run.

Low Supply

Temp Cutoff

Alarm

BI: 35

The Supply Air has fallen

below the Low SAT Cutoff
Setpoint and cooling stages

will begin to deactivate. If the

unit is in Economizer, Vent,

or Heating Mode the Supply

Fan will shut off.

High Control

Mode Alarm

BI: 36

Occurs when the

Controlling Sensor

Temperature rises above

the Cooling Mode Enable

Setpoint plus the Control

Mode High Alarm Offset.

Applies only to Space or

Return Air Temperature

controlled units.

Low Control
Mode Alarm

BI: 37

Occurs when the

Controlling Sensor

Temperature falls below

the Heating Mode Enable

Setpoint minus the Control

Mode Low Alarm Offset.

Applies only to Space or

Return Air Temperature

controlled units.

VCC-X BACnet

®

Parameters