VCC-X Controller Technical Guide

APPENDIX C - RSMV LCD SCREENS

93

Diagnostic Screens

Diagnostic Screens

Refer to the following map when navigating through the Diagnostic
Screens. From the DIAGNSTC Screen, press

<ENTER> to scroll

through the screens.

DIAGNSTC

WDOG CNT

#

PWER CNT

#

WATCH DOG TIMER

Displays the number of times the board has been reset due

to watchdog timer overfl ow.

POWER LOSS COUNT

Displays the number of times the board has been reset due

to power loss.

SP VLT

X.XX

SUCTION PRESSURE SENSOR VOLTAGE

Displays the current voltage of the Suction Pressure Sensor.

HP VLT

X.XX

HEAD PRESSURE SENSOR VOLTAGE

Displays the current voltage of the Head Pressure Sensor.

BIN 1 - BIN 4

ON/OFF

BINARY INPUTS #1 - #4

Displays the current status of each Binary Input.

TMP1 VLT

X.XX

COIL TEMPERATURE SENSOR 1 VOLTAGE

Displays the current voltage of the 1st Coil Temperature Sensor.

TMP2 VLT

X.XX

COIL TEMPERATURE SENSOR 2 VOLTAGE

Displays the current voltage of the 2nd Coil Temperature Sensor.