Refrigerant system module wiring, Rsmv inputs & outputs wiring, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual

Page 39: 24 vac only, Head pressure control, Coil temperature sensors

Advertising
background image

VCC-X Controller Technical Guide

REFRIGERANT SYSTEM MODULE WIRING

39

RSMV Inputs & Outputs Wiring

M

ENTER

UP

DOWN

ALARM

MENU

OE370-26-RSMV

REFRIGERANT

SYSTEM MODULE V

AAON No.: V42440

E-BUS

E-BUS

+24

V

AC

GND

RELAY CONTACT
RATING IS 1 AMP

MAX @ 24 VAC

CONDENSER

COMP 1
COMP 2

EXPANSION

VALVE 1

SUCTION

PRESSURE

SENSOR

HEAD

PRESSURE

SENSOR

COIL TEMP

SENSORS

BINARY
INPUTS

EXPANSION

VALVE 2

ANALOG

OUTPUTS

BLACK

+5 V

+5 V

COIL TEMP 1

COMP STATUS 1

BLACK

MOD COMP SIG

CONDENSER FAN SIG

WHITE

SP

HP

COIL TEMP 2

COMP

2

STATUS

GND

GND

TEMP 3

OUTSIDE COIL TEMP. SW
BIN 4

GND

GND

WHITE

RED

RED

GND

GREEN

GREEN

REVERSING VALVE

COMMON

RELAY OUTPUT

TERMINALS

www.aaon.com

WattMaster Overlay #000065 Rev 1A

SW

REFRIGERANT SYSTEM MODULE

FOR VFD COMPRESSORS

(RSMV)

24VAC

GND

Line
Voltage

Size Transformer For
Correct Total Load.
RSMV = 18 VA

NOTE:

ALL RELAY OUTPUTS ARE NORMALLY

OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

CONDENSER ENABLE

COMPRESSOR 2 ENABLE

COMPRESSOR 1 ENABLE

24 VAC ONLY

R1

R3

R2

COMM

RD

WH

BK

GRN

RD

WH

BK

GRN

EXPANSION

VALVE 1

EXPANSION

VALVE 2

COM

+

MODULATING

COMPRESSOR

COM

+

CONDENSER

FAN SIGNAL

AOUT1
AOUT2
GND

Figure 24: RSMV Outputs Wiring

Suction Pressure Sensor Wiring

The OE275-01 Suction Pressure Transducer must be wired as shown
in Figure 23. It is typically required for all VCC-X applications.

The Suction Pressure Sensor is used to measure suction pressure
at the HVAC unit’s DX evaporator coil suction line. This suction
line pressure is converted to saturated refrigerant temperature by
the RSMV Controller. This temperature is used by the RSMV to
accurately control the Expansion Valves to maintain Superheat to
provide optimum performance of the system.

CAUTION:

The Shraeder port used for installation of the

suction pressure transducer should be located in a vertical

position of the suction line to prevent refrigerant oil from

accumulating in the sensor.

Head Pressure Control

The RSMV can monitor a Head Pressure Transducer and control
Condenser Fans to maintain a Head Pressure Setpoint. The Condenser
Fan will be controlled with a 0-10 VDC output signal.

Coil Temperature Sensors

The Coil Temperature Sensors are used to measure Coil Temperature
after each evaporator coil line. This temperature combined with the
calculated saturated refrigerant temperature is used to calculate the
Superheat of each individual evaporator coil. The Superheat is used
to drive the Expansion Valves to maintain a given Superheat Setpoint.