Vcc-x controller wiring, Outdoor air temperature sensor wiring, Vcc-x controller technical guide 30 – Orion System VCC-X Controller User Manual

Page 30: Outdoor air temperature sensor

Advertising
background image

Zone

Zone

VCC-X CONTROLLER WIRING

VCC-X Controller Technical Guide

30

Outdoor Air Temperature Sensor Wiring

OE250

Outdoor Air

Temperature Sensor

AI7

GND

Make Splice Connections

Inside Sensor Enclosure

As Shown. Seal All Conduit

Fittings With Silicone

Sealant

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

VCC-X Controller

Outdoor Air Temperature Sensor

The OE250 Outdoor Air Temperature Sensor must be wired as shown
for proper operation of the VCC-X Controller. The Outdoor Air
Temperature Sensor is a 10K Type III thermistor sensor. The sensor
should be mounted in the upright position as shown in an area that
is protected from the elements and direct sunlight. Be sure to make
the wiring splices inside of the Outdoor Air Temperature Sensor
weather-tight enclosure. See Figure 16 below for details.

Figure 16: OE250 – Outdoor Air Temperature Sensor Wiring

For applications involving Outdoor Air Humidity, the OE265-15-A
or OE265-16-A E-BUS Outside Air & Humidity Sensor must be
used instead. See Figures 17 for details.

CAUTION:

Be sure to mount the Outdoor Air Temperature

Sensor in an area that is not exposed to direct

sunlight. The shaded area under the HVAC unit

rain hood is normally a good location. Unused

conduit opening(s) must have closure plugs

installed and must be coated with sealing com-

pound to provide a rain-tight seal. Water can

damage the sensor.

Advertising