AIRFLOW MONITORING

WIRING

45

NOTE:

The Airfl ow Station’s baud rate needs to be set to
19,200 in order to communicate with the VCC-X
Controller.

NOTE:

Up to 4 EBTRON

®

, GreenTrol

TM

, or Paragon

Airfl ow Measurement Digital Transmitters can be
attached to each Adapter Board.

NOTE:

If using multiple E-BUS Sensors or Modules, the

E-BUS Hub (HZ-EBC-248 or MS000248) may be
required.

*NOTE:

When confi guring the GTC116 Series, be sure to set

the Parity to “NO PARITY, 1 STOP BIT.”

EBTRON

®

, GreenTrol

TM

, and Paragon Wiring

Figure 30: EBTRON

®

GTC116 Series, GreenTrol

TM

GA-200-N Series, and Paragon MicroTrans

EQ

Series Air

Flow Measurement Digital Transmitter Wiring

EBTRON

®

, GreenTrol

TM

, and Paragon

Air Flow Measurement Digital

Transmitters

NOTE:

Only the EBTRON

®

GTC116 series, GreenTrol

TM

GA-200-N Module (with GF series Airfl ow Station),
or Paragon MicroTrans

EQ

series of MODBUS trans-

mitters are compatible with the VCC-X Controller.
No other series of transmitters will work for this
application. Contact WattMaster Controls for infor-
mation on other airfl ow station options.

The OE365-15-EBA E-BUS Adapter Board attaches to the VCC-X
Controller with an EBC E-BUS cable. The Adapter Board is used
for connecting the EBTRON

®

, GreenTrol

TM

, or Paragon Airfl ow

Measurement Digital Transmitter to the VCC-X Control System.
You must wire the Airfl ow Measurement Digital Transmitter to the
Adapter Board as shown in Figure 30.

WARNING!!

Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.

COMM

COMM

COMM

NET-

NET-

NET-

NET+

NET+

NET+

Airflow Measurement

Digital Transmitter Terminals

For Outdoor Air CFM

(Set Address Switch To 9)

Airflow Measurement

Digital Transmitter Terminals

For Return Air CFM

(Set Address Switch To 10)

Airflow Measurement

Digital Transmitter Terminals

For Supply Air CFM

(Set Address Switch To 11)

COMM

NET-

NET+

Airflow Measurement

Digital Transmitter Terminals

For Exhaust Air CFM

(Set Address Switch To 12)

24VAC

GND

Line
Voltage

Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA

E-BUS Cable

(EBC Cable)

VCC-X Controller

OE365-15-EBA

E-BUS Adapter Board

NOTE: Set Airflow Monitoring
Station’s Baud Rate To 19,200
In Order To Communicate
With The VCC-X.