Vcc-x controller wiring, Return air temperature sensor wiring – Orion System VCC-X Controller User Manual

Page 27

Advertising
background image

VCC-X Controller Technical Guide

VCC-X CONTROLLER WIRING

27

Return Air Temperature Sensor Wiring

Return Air Temperature Sensor

The OE231 Return Air Temperature Sensor must be wired as shown
for proper operation. The Return Air Temperature Sensor is a 10K
Type III thermistor sensor. The Return Air Temperature Sensor
should be mounted in the return air duct. If the system has a Zoning
Bypass Damper installed, be sure the return air sensor is located
upstream of the bypass duct connection. See Figure 13 below for
details.

Mount In HVAC

Unit Return

Air Duct

OE231 Return Air Temperature Sensor

AI4

GND

VCC-X Controller

Figure 13: OE231 – Return Air Temperature Sensor Wiring

Advertising