REFRIGERANT SYSTEM MODULE WIRING

VCC-X Controller Technical Guide

38

Refrigerant System Module for VFD

Compressors Wiring

The OE370-26-RSMV Refrigerant System Module for VFD
Compressors (RSMV) monitors and controls one refrigeration circuit
of the HVAC unit. The module is designed for R410-A refrigerant.

The RSMV is connected to the VCC-X Controller (Orion Part No.
OE338-26B-VCCX; AAON Part No. V42430). Up to 4 RSMV’s
can be connected, depending on the size of the system. There are
2 E-BUS Expansion Ports which allow the use of communicating
sensors and the E-BUS Modules.

The RSMV provides 4 analog inputs, 3 binary inputs, 3 relays, and
4 analog outputs. See Figure 23 below for inputs wiring and Figure
24, page 39
for outputs wiring.

M

ENTER

UP

DOWN

ALARM

MENU

OE370-26-RSMV

REFRIGERANT

SYSTEM MODULE V

AAON No.: V42440

E-BUS

E-BUS

+24

V

AC

GND

RELAY CONTACT
RATING IS 1 AMP

MAX @ 24 VAC

CONDENSER

COMP 1
COMP 2

EXPANSION

VALVE 1

SUCTION

PRESSURE

SENSOR

HEAD

PRESSURE

SENSOR

COIL TEMP

SENSORS

BINARY
INPUTS

EXPANSION

VALVE 2

ANALOG

OUTPUTS

BLACK

+5 V

+5 V

COIL TEMP 1

COMP STATUS 1

BLACK

MOD COMP SIG

CONDENSER FAN SIG

WHITE

SP

HP

COIL TEMP 2

COMP

2

STATUS

GND

GND

TEMP 3

OUTSIDE COIL TEMP. SW
BIN 4

GND

GND

WHITE

RED

RED

GND

GREEN

GREEN

REVERSING VALVE

COMMON

RELAY OUTPUT

TERMINALS

www.aaon.com

WattMaster Overlay #000065 Rev 1A

SW

SP

GND

+V

BK

RD
WH

HP

GND

+V

BK

RD
WH

SUCTION PRESSURE

SENSOR

HEAD PRESSURE

SENSOR

(BY OTHERS)

REFRIGERANT SYSTEM MODULE

FOR VFD COMPRESSORS

(RSMV)

COIL

TEMP. 2 SENSOR

(SUCTION LINE)

TEMP1

GND

TEMP2

COMPRESSOR STATUS 1

COMPRESSOR STATUS 2

BIN1
BIN2

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
RSMV = 18 VA

GND

COIL (SUCTION LINE)

TEMP. 1 SENSOR

RSMV Inputs & Outputs Wiring

Figure 23: RSMV Inputs Wiring

The RSMV Module provides the following:

Controls the Compressors to satisfy the Supply Air

Temperature Setpoint (Supply Air Temperature sent

by VCC-X Controller) during Cooling Mode. During

Dehumidifi cation Mode, it controls the Compressors

to the Suction (Saturation) Temperature Setpoint

Modulates the Condenser Fan to maintain the Head

Pressure

Setpoint

Modulates the Expansion Valves to maintain the

Superheat

Setpoint

Provides alarms and safeties for the compressor and

condenser

operation.

Contains a 2 x 8 LCD character display and 4

buttons that allow for status display, setpoint changes,

and

confi guration changes.