Preheat-x controller wiring, Vcc-x controller technical guide 48, Leaving air temperature setpoint – Orion System VCC-X Controller User Manual

Page 48: Entering air temperature setpoint, Preheat enable signal, Leaving air temperature status, Entering air temperature status, Alarm status

Advertising
background image

PREHEAT-X CONTROLLER WIRING

VCC-X Controller Technical Guide

48

PREHEAT-X Controller Wiring

Figure 33: PREHEAT-X Controller to VCC-X Controller Wiring

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

#LB102XXX-A

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

OAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

AIN1

Entering Air Temperature

Sensor

Reset In

0-10 VDC

GND

+

-

Emergency

Shutdown

Line

GND

24V

AC

40 VA

Transformer

Minimum

Heat 1 Relay

Heat 2 Relay

Heat 3 Relay

Heat 4 Relay

Heat 5 Relay

Heat 6 Relay

COM

Alarm

Note:
All Relay Outputs Are
Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

Relay
Contact

PWM SSR

+

Modulating SCR

(0-10 VDC)

+

PREHEAT-X CONTROLLER

(OE377-26-00061)

AIN2
AIN3

RST

GND
GND

BIN1
BIN2

Leaving Air 2

Temperature Sensor

Leaving Air 1

Temperature Sensor

SAFETIES

(BY OTHERS)

N.C.

Heat Enable

Signal (24 VAC)

W1

NOTE: Reset In And Heat

Enable Inputs Are Used In

Stand-Alone Mode Only

Mount Inside PREHEAT-X

Box Wall

Make Splice

Connections

Inside Sensor

Enclosure

As Shown. Seal All

Conduit Fittings With

Silicone Sealant

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Mount Inside PREHEAT-X

Box Wall

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

Rev.: 1D

#S

000062

W

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

EAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24 V

A

C

GND

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

www.orioncontrols.com

MSTP

BACnet

EBC E-BUS Cable

Connects To

VCC-X Controller’s

Expansion Port

PREHEAT-X Controller Wiring

The OE377-26-00061 PREHEAT-X Controller (AAON Part No.
V48510) is designed to control fi xed stages of Preheat and optional
modulating Preheat to maintain a desired Preheat Leaving Air
Temperature Setpoint. The PREHEAT-X Controller directly connects
to the VCC-X Controller or indirectly using an E-BUS Expansion
Board via an EBC E-BUS cable. See Figure 33 for wiring.

The following information will be passed between the PREHEAT-X
Controller and the VCC-X Controller:



Leaving Air Temperature Setpoint



Entering Air Temperature Setpoint



Preheat Enable Signal



Leaving Air Temperature Status



Entering Air Temperature Status



Alarm Status



If the communication is interrupted between the

PREHEAT-X Controller and the VCC-X Controller,

the PREHEAT-X controller will be disabled.

For more information, refer to the PREHEAT-X Controller Technical
Guide.

NOTE:

If using multiple E-BUS Sensors or Modules, the

E-BUS Hub or Adapter Board may be required.