Vcc-x controller wiring, Building pressure control output wiring, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual

Page 37: Building pressure control output

Advertising
background image

VCC-X Controller Technical Guide

VCC-X CONTROLLER WIRING

37

Building Pressure Control Output Wiring

Figure 22: Building Pressure Control Output Wiring Diagram

Building Pressure Control Output

The Building Pressure Control Output is a 0-10 VDC or 2-10 VDC
signal sent from the VCC-X Controller. When using the output for
Direct Building Pressure Control (output signal rises on a rise in
building pressure), the output signal can be connected to either a
Variable Frequency Drive controlling an exhaust fan or to a damper
actuator controlling an exhaust damper (both by others). When used
in this manner, the output signal must be confi gured for Direct Acting
operation. See Figure 22 below for detailed wiring of the Building
Pressure Control Output Signal.

When using this output for Reverse Building Pressure Control
(output signal rises on a fall in building pressure), a damper
actuator controlling an OA Damper or Supply Fan VFD would be

used. When using the OA damper for Reverse Building Pressure
Control, the output signal must be confi gured for Reverse Acting
operation. A Building Pressure Sensor connected to AI5 on the
VCC-X Controller is used to sense and control the signal to the
Building Pressure Output. The OE258-01 Building Static Pressure
Sensor must be connected in order for the Building Pressure Output
to operate correctly.

CAUTION:

Variable Frequency Drive units can cause

large transient noise spikes that can cause interference to be

propagated on other electronic equipment. Use shielded wire

wherever possible and route all sensor and controller wiring

away from the Variable Frequency Drive and the HVAC unit

electrical wiring.

VCC-X Controller

AOUT4

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA

0-10 VDC Input From AO1

GND

GND

Shield

Shield

24 V

A

C

GND

+

+

Building Pressure Control

Exhaust Fan Variable Frequency Drive

(By Others)

_ GND

Caution: The VFD Unit Must Be
Configured For 0-10VDC Input. The Input
Resistance At The VFD Must Not Be
Less Than 1000 Ohms When Measured
At The VFD Terminals With All Input
Wires Removed.

Building Pressure Control

Damper Actuator

(By Others - Belimo Actuator Shown)

Wiring When Using Damper Actuator

For Building Pressure Control

Both Types Of

Building

Pressure Control

Devices Are

Shown

Only One Type

Of Building

Pressure Control

Device May Be

Used On Each

HVAC Unit

Wiring When Using Exhaust Fan VFD

For Building Pressure Control

3 Y1

2

1 - COM

1 - COM

Belimo Actuator Wiring

Shown. Consult

Factory For Other

Manufacturer Wiring

Instructions

+

Note:
Wire To The VFD Using 18 GA
Minimum 2 Conductor Twisted Pair
With Shield Cable. Wire Shield To
GND As Shown

GND