Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 102: Vcc-x controller technical guide 102

Advertising
background image

APPENDIX D - VCC-X BACnet

®

VCC-X Controller Technical Guide

102

VCC-X BACnet

®

Parameters

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Indoor

Humidity

Setpoint Low

Reset Limit

AV: 53

On indoor controlled (non

MUA) units, this is the

Humidity setpoint that

initiates Dehumidifi cation.

During Coil Temp Reset,

this is the lowest Space

RH value that corresponds

to the High Coil Temp

Setpoint.

0

100

Indoor

Humidity

Setpoint High

Reset Limit

AV:54

During Coil Temp Reset,

this is the highest Space

RH value that corresponds

to the Low Coil Temp

Setpoint.

0

100

Duct Static

Pressure
Setpoint

AV:55

Current Static

Pressure Setpoint.

.10

3.0

Duct Static

Pressure

Control

Deadband

AV:56

Value above and below

the Duct Static Pressure

Setpoint where no control

change occurs.

.01

.5

Building

Pressure

Control

Setpoint

AV:57

Building

Pressure Setpoint.

-.20

.20

Building

Pressure

Control

Deadband

AV:58

Value above and below the
Building Pressure Setpoint

where no control change

occurs.

.01

.1

Minimum

Outdoor Air

CFM

AV:59

Minimum Outdoor Airfl ow

CFM Setpoint

.10K

200K

Outdoor Air

CFM

Proportional

Window

AV:60

Controls rate of change

for damper signal. As OA

CFM moves further from

setpoint within this window,

the damper makes a larger

change.

10

9999

SZ VAV Fan

Speed Integral

AV:61

The Integral Constant for

Single Zone VAV Fan

Control.

0

10

Relay Run-

time Limit

AV:62

If any confi gured relay’s run

time exceeds this number of

hours of operation, a

warning alarm is generated

so that periodic

maintenance can be

performed.

0

30000

Schedule

Force

AV: 63

0 = Auto (uses controller’s

schedule)

1 = Forced

Occupied

2 = Forced Unoccupied

0

2

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

HVAC Mode

Override

AV: 64

Overrides normal controller

operation in order to force

the unit into this desired

mode. Confi guring for

“Auto” will restore normal
unit control of the mode of

operation.

0=Auto

1=Vent

2=Cool
3=Heat

4=Vent

Dehum.

5=Cool

Dehum.

6=Heat

Dehum.

Fan VFD

Override

AV: 65

Override to force the VFD

to this percentage speed.
Confi guring “Auto” will

restore normal unit control

of the VFD speed.

0%

100%

Auto=65535

Outdoor Air

Damper

Override

AV: 66

Overrides all other Outdoor

Air Damper position

commands so as to maintain

this fi xed position.

Confi guring for “Auto” will

restore normal unit control

of the Outdoor Air Damper/

Economizer operation.

0%

100%

Auto=65535

Cooling
Enabled

Status

BI: 1

Status that indicates

Mechanical Cooling is

enabled based on the

Cooling Lockout.

Heating

Enabled

Status

BI: 2

Status that indicates that

Mechanical Heating is

enabled based on the

Heating Lockout.

Economizer

Enabled

Status

BI: 3

Status that indicates

the Economizer is enabled

based on the Economizer

Enable Setpoint.

Reheat

Enabled

Status

BI:4

Modulating Hotgas Reheat

Enabled.

Emergency

Heat Enabled

Status

BI:5

Shows the Emergency

Heat is enabled based on

the Compressor Heating

Lockout.

Proof of

Airfl ow

BI:6

Proof of Airfl ow Binary

Input Status

Exhaust Hood

On/Off Status

BI:7

Exhaust Hood On/Off

Binary Input Status

Remote Force

Occupied

BI:8

Remote Forced Occupied

Mode Binary Input Status

Remote Force

Cooling

BI:9

Remote Forced Cooling

Mode Binary Input Status

Remote Force

Heating

BI:10

Remote Forced Heating

Mode Binary Input Status

Remote Force

Dehumidifi ca-

tion

BI:11

Remote Force

Dehumidifi cation Mode

Binary Input Status

Bad Supply

Air Sensor

BI: 12

Alarm that indicates a

failure of the Supply Air

Sensor.