Vcc-x controller wiring, Building pressure sensor wiring, Vcc-x controller technical guide 28 – Orion System VCC-X Controller User Manual

Page 28: Building pressure sensor, Zone

Advertising
background image

Zone

Zone

VCC-X CONTROLLER WIRING

VCC-X Controller Technical Guide

28

Building Pressure Sensor Wiring

Figure 14: OE258-01 Building Pressure Sensor Wiring Diagram

Building Pressure Sensor

The OE258-01 Building Static Pressure Sensor must be wired as
shown in Figure 14 below. There are 3 terminal connections on the
Building Pressure Sensor. Connect the power side of the 24 VAC
power source to the terminal labeled “+ EXC.” Connect the GND
side of the 24 VAC power source to the terminal labeled “- COM.”
Connect the remaining terminal labeled “OUT” to AIN5 on the
VCC-X Controller.

WARNING:

It is very important to be certain that all wiring

is correct as shown in the wiring diagram below. Failure to

observe the correct polarity will result in damage to the HVAC

Unit Controller, Building Pressure Sensor, and the VCC-X

Controller.

AI5

GND

VCC-X Controller

EXC

COM

OUT

LOW

-

+

+

+

Tubing To Building
Pressure Sensing Location

Tubing To Atmospheric
Pressure Sensing Location

-

+

OE258-01 Building Static

Pressure Sensor

HIGH

To 24

VAC