Overview, System features – Orion System VCC-X Controller User Manual

Page 5

Advertising
background image

OVERVIEW

5

VCC-X Controller Technical Guide

System Features

Features

The VCB-X Controller (OE335-26B-VCBX-A) is designed with 5
analog inputs, 3 analog outputs, 1 triac output, 4 binary inputs, and 6
relay outputs. It also has an on-board BACnet

®

port for connection to

an MS/TP network. The Controller contains a 2 x 8 LCD character
display and 4 buttons that allow for status and alarm display and
force modes as well as BACnet confi guration.

The VCB-X EM1 Expansion Module (OE336-23-EM1-A) provides
an additional 6 analog inputs, 4 analog outputs, 3 binary inputs,
and 5 confi gurable relay outputs. The VCB-X EM2 Expansion
Module (OE336-23-EM2-A) provides an additional 1 analog
input, 2 analog outputs, and 3 binary inputs. The VCB-X 12
Relay Expansion Module (OE358-23E-12R-A) provides up to 12
additional confi gurable relay outputs.

There are also 2 E-BUS Expansion Ports which allow for
the connection of the three expansion modules listed above,
communicating sensors, an EBTRON

®

or GreenTrol

TM

Airfl ow

Monitoring system, and future E-BUS Modules via modular cable
assemblies. There are presently 5 communicating sensors available.
Two of these sensors have LCD displays: E-BUS Digital Space
Temperature Only Sensor or E-BUS Digital Space Temperature
and Humidity Sensor. There is a communicating E-BUS Space
Temperature and Humidity Sensor with no LCD display as well as
an E-BUS Space CO

2

Sensor, and E-BUS Duct CO

2

Sensor with

no LCD display.

The VCB-X Controller provides for Constant Volume, VAV, Single
Zone VAV, MUA, and Air to Air Heat Pump applications.

Most common HVAC unit control applications can be confi gured
using only the VCB-X Controller. If the application requires more
inputs and/or outputs, the optional expansion modules are available
to provide for additional analog, binary, or digital inputs and outputs
as required.

Other features of the VCB-X include:

Up to 5 Total Stages of Heating and Cooling

Direct Digital Control of Copeland Digital

Scroll™

Compressor

Modulating Cooling Output for Chilled Water

Valve

Control

Modulating Heating Output ( Hot Water Valve,

Steam Valve, SCR Electric Heat Control)

Full Integration with the AAON

®

MODGAS-X

Modulating Natural Gas Controller

Full Integration with the AAON

®

MHGRV-X

Modulating Hot Gas Reheat Controller

Confi gurable for Heat Pump Applications

Heat Pump Defrost Operation

Advanced Dehumidifi cation Capabilities

Auxiliary and Emergency Heat Options for Heat

Pumps

Air Flow Monitoring of Outdoor Air, Supply Air,

Return Air, and Exhaust Air Streams

Air Flow Control of Outdoor Air Damper

Single Zone VAV Control w/Optional CAV Heating

Primary/Secondary Heating Control

Remote Forced Cooling, Heating, and

Dehumidifi cation Control

Remote SAT Reset Signal

Return Air Bypass Control

Adaptive Supply Air Reset

Selectable Mode Enable Sensor

Fan Proving Interlock

Dirty Filter Alarm

Emergency Shutdown Input (Smoke Detector/

Firestat or other Shutdown Conditions)

Drybulb/Wetbulb/Dewpoint Control of Economizer

Operation

Building Pressure Control (Direct or Reverse

Acting)

Remote Forced Occupied Capability

Confi gurable for AAON

®

PAC and DPAC Applications

IAQ Economizer Reset

Title 24 Economizer Certifi ed

7-Day, 2-Event-per-Day Scheduling

14 Holiday Event Scheduling

Daylight Savings Time Adjustment

Trend Logging Capability

Static Pressure Control for Filter Loading

Applications

Heat Wheel - On/Off Control

Head Pressure Control

Water Source Heat Pump Monitoring

On-board BACnet

®

port for connection to an

MS/TP network (See Appendices B & C)

Advertising
This manual is related to the following products: