Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual

Page 99: Vcc-x controller technical guide

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX D - VCC-X BACnet

®

99

VCC-X BACnet

®

Parameters

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Preheater

Reset Input

AI: 78

Current Entering Air Temp

for Preheater

Preheater Mod

Heat Signal

AI: 79

Current Modulating Heat

Signal for Preheater

Preheater

PWM Signal

AI: 80

Current PWM Output

Signal for Preheater

Occupied

Cooling

Setpoint

AV: 1

If the control temperature

rises one degree above this

setpoint, the control will

activate the cooling de-

mand. If the control sensor

is the Supply Air Sensor,

then the cooling demand is

always active.

1

110

Occupied

Heating

Setpoint

AV: 2

If the control temperature

drops one degree below

this setpoint, the control

will activate the heating

demand. If the control

sensor is the Supply Air

Sensor, then there is no

heating demand.

1

110

Hood On

Outdoor

Air Cooling

Setpoint

AV:3

This is the Cooling Mode

Enable Setpoint used only

in Hood On Mode or Space

Temperature Control of

High Percentage Outdoor

Air Units.

1

110

Hood On

Outdoor

Air Heating

Setpoint

AV:4

This is the Heating Mode

Enable Setpoint used only

in Hood On Mode or Space

Temperature Control of

High Percentage Outdoor

Air Units.

1

110

Unoccupied

Cooling Offset

AV:5

During the Unoccupied

Mode of Operation, this

Setpoint offsets the

Occupied Cooling Setpoint

up by this user-adjustable

amount. If you do not want

Cooling to operate during

the Unoccupied Mode, use

the default setting of 30°F

for this setpoint.

0

30

Unoccupied

Heating Offset

AV:6

During the Unoccupied

Mode of Operation, this

Setpoint offsets the

Occupied Heating

Setpoint down by this user-

adjustable amount. If you

do not want Heating to

operate during the

Unoccupied Mode, use the

default setting of 30°F for

this setpoint.

0

30

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Mode Select

Deadband

AV:7

This value is added to and

subtracted from the HVAC

Mode Setpoints to create a

control deadband range.

0

10

Max Coil

Setpoint

Reset Limit

AV:8

This is the highest that the

Coil Temperature will be

reset to during Space

Humidity Reset of the Coil

Suction Temperature

Setpoint. If no coil

temperature reset is

required, this value should
be set the same as the Min

Coil Reset Limit.

35

70

Min Coil

Setpoint Reset

Limit

AV:9

This is the lowest that the

Coil Temperature will be

reset to during Space

Humidity Reset of the

Coil Suction Temperature

Setpoint. If no coil

temperature reset is

required, this value should

be set the same as the Max

Coil Reset Limit.

35

70

Supply Air

Cooling

Setpoint

AV:10

Supply Air Cooling

Setpoint. If Supply Air

Reset is confi gured this is

the Low SAT Cooling Reset

Value.

30

80

Supply Air

Heating

Setpoint

AV:11

Supply Air Heating

Setpoint. If Supply Air

Reset is confi gured this is

the Low SAT Heating Reset

Value.

40

240

Max SAT

Cooling

Setpoint Reset

Limit

AV: 12

If Supply Air Reset is

confi gured this is the High

SAT Cooling Reset Value.

0

100

Max SAT

Heating

Setpoint Reset

Limit

AV: 13

If Supply Air Reset is con-

fi gured this is the High SAT

Heating Reset Value.

0

250

Supply Air

Cooling

Staging

Window

AV: 14

In Cooling Mode, if the

Supply Air Temperature

drops below the Active

Supply Air Cooling Setpoint

minus this Staging Window,

a Cooling Stage will be

deactivated after its

Minimum Run Time.

1

30

Supply Air

Heating

Staging

Window

AV: 15

In Heating Mode, if the

Supply Air Temperature

rises above the Active

Supply Air Heating Setpoint

plus this Staging Window, a

Heating Stage will be

deactivated after its

Minimum Run Time.

1

50