1) preparation, 2) operating procedure – Yaskawa Sigma-5 User Manual: Operation of Digital Operator User Manual

Page 81

Advertising
background image

3.2 Operations

3-47

9

head1

3

Utility Function Mode

(1) Preparation

The following conditions must be met to initialize the vibration detection level.

• The write prohibited setting (Fn010) must not be set to write-protect parameters.
• The test without a motor function must be disabled (Pn00C.0 = 0).

(2) Operating Procedure

Use the following procedure.

• The vibration may not be detected because of improper

servo gains. Also, not all kinds of vibrations can be
detected. Use the detection result as a guideline.

• Set a proper moment of inertia ratio (Pn103). Improper

setting may result in the vibration alarm, warning misde-
tection, or non-detection.

• The references that are used to operate your system must

be input to execute this function.

• Execute this function under the operating condition for

which the vibration detection level should be set.

• Execute this function while the motor speed reaches at

least 10% of its maximum.

Step

Display after Operation

Keys

Operation

1

Press the

Key to view the main

menu for the utility function mode.
Use the

or

Key to move

through the list and select Fn01B.

2

Press the

Key. The display changes

to the Fn01B execution display.

3

Press the

Key.

“Init” is displayed flashing, and the vibra-

tion level is detected and initialized.
Note: Continues initialization until the

Key is pressed again.

R U N

− F U N C T I O N −

F n 0 1 4 : O p t I n i t

F n 0 1 B : V i b l − v l I n i t

F n 0 1 E : S v M o t O p I D

F n 0 1 F : F B O p M o t I D

L e v e l I n i t

R U N

V i b r a t i o n D e t e c t

S t a r t : [ D A T A ]
R e t u r n : [ S E T ]

L e v e l I n i t

R U N

V i b r a t i o n D e t e c t

I n i t