3.2 Operations

3-53

9

head1

3

Utility Function Mode

3.2.23 Origin Setting (Fn020)

When using an external absolute encoder for fully-closed loop control, this function
is used to set the current position of the external absolute encoder as the origin (zero
point position).

This function can be used with the following products.

Mitutoyo Corporation
ABS ST780A series
Model: ABS ST78†A/ST78†AL

(1) Preparation

The following conditions must be met to set the origin.

• The write prohibited setting (Fn010) must not be set to write-protect parameters.
• The servomotor power must be OFF.

(2) Operating Procedure

Use the following procedure.

∗ With SGDV SERVOPACK that support MECHATROLINK, “A.941” will not be shown, and

“BB” will be displayed instead.

Step

Display after Operation

Keys

Operation

1

Press the

Key to view the main

menu for the utility function mode.
Use the

or

Key to move

through the list and select Fn020.

2

Press the

Key. The display changes

to the Fn020 execution display.

3

Press the

or

Key to

“ORGSET5”.

4

Press the

key to start setting the ori-

gin. The message, “Scale Origin Set,”

flashes while the origin is being set. After

the origin has been successfully set, the

displayed status changes as follows: “BB”

to “DONE” to “A.941*”.

5

Turn OFF the power and then turn it ON again to validate the new setting.

B B

− F U N C T I O N −

F n 0 1 F : F B O p M o t I D

F n 0 2 0 : S

− O r i g S e t

F n 0 3 0 : S o f t R e s e t

F n 0 8 0 : P o l e D e t e c t

O R G S E T 1

B B

S c a l e O r i g i n S e t

O R G S E T 5

B B

S c a l e O r i g i n S e t

B B

S c a l e O r i g i n S e t