Operating Instructions Powador XP100-HV

Page 17

I n s t a l l a t i o n / S t a r t - u p

5.3.2

Connecting to the external transformer (AC connection)

The inverter is connected to the power grid using a 3-phase connection. The connection for the power grid is
located in the right side of the housing, at the bottom (fi gure 8).

Connection data

Max. cable diameter

300 mm²

Tightening torque for AC terminal connections

43 Nm

Cable Lug hole size

12 mm ~ 14 mm

Connect the cables

Each cable corresponds to one phase.

 Guide the cables through the opening.

Be sure to connect each of the cables to the correct terminal.

 Screw down the cables.

 Check to make sure that all of the cables are securely attached.

Figure 8: AC connection