3 frequency dependant power reduction enable on – KACO Powador XP100-HV User Manual

Page 59

Advertising
background image

Operating Instructions Powador XP100-HV

Page 59

P a r a m e t e r

8.3.3

Frequency Dependant Power Reduction Enable On

Grid Over Frequency

Figure 50: Grid over frequency

PM : Instantaneously Available Power

ΔP : Power Reduction (Power Reduction Gradient Level)

This function controls active power which is proportional to Grid frequency increase. As you can see in the picture,
active power need to be restricted if grid frequency is over 50.2 Hz. PM (Instantaneously available power) decrea-
ses with 40 %/Hz slope and it can be restorable if grid frequency is less than 50.05 Hz.

When this function is activated, the protection function for “Grid Over Frequency Level 1” is disabled and the pro-
tection function for “Grid Over Frequency Level 2 and “Grid Over Frequency Level 3” is enabled.