Operating Instructions Powador XP100-HV

Page 67

P a r a m e t e r

Parameters

Units

Ranges

Descriptions

Default

COSPHI Control
Mode

-

0 ~ 5

Reactive power supply method in Internal mode
and RPC mode

0: disabled

1: fi xed P

2: fi xed cos

3: fi xed Q

4: Cos(P/Pn)

5: Q(U)

2

COSPHI Internal
Power Factor

-

-0.999 ~ 1

Power factor reference in internal mode

1

COSPHI Internal
Reactive Power

%

-99.9 ~ 99.9

Reactive power reference in internal mode (Percent
for rated one)

0

COSPHI Actual
Power Factor

-

-0.999 ~ 1

The actual power factor value that is applied (Read
only)

1

COSPHI RPC Power
Factor

-

-0.999 ~ 1

Power factor reference in RPC mode

1

COSPHI RPC Reactive
Power

%

-99.9 ~ 99.9

Reactive power reference in RPC mode
(percent for rated one)

0

COSPHI Stray Ratio

-

0 ~ 2

The setup value for COSPHI control

0.985

Positive Sequence
PLL Enable

-

On(1), Off (0)

The use of grid voltage of positive sequence at PLL 1

FRT K Factor

-

0 ~ 10

The setup constant during FRT control

2

FRT IQ Ramp

ms

0 ~ 99999

The slope of active power supply during FRT
control

4000

FRT IQ Ramp Time

ms

0 ~ 99999

The time that use a slope changed by FRT IQ ramp
parameter

2000

Positive Sequence
LPF

Hz

0 ~ 100

The cutoff frequency for RMS value of positive
sequence

100

PLL Freq LPF

Hz

0 ~ 100

The cutoff frequency for frequency value detection
of PLL

100

Q(V) Control Target
Voltage

V

208 ~ 440

Value of Q(V) Control Target Voltage

380

Q(V) Control K Factor -

0 ~ 50

A setup constant for voltage control of BDEW

3.1

Q(V) Control
Deadband

%

0 ~ 100

Non-applicable voltage range during voltage
control of BDEW

1

Q(V) Control Ramp
Time

sec

0 ~ 99999

The slope of reactive current increase during
voltage control of BDEW

60

Table 17: Controller Parameters