F a u l t s a n d W a r n i n g s

F a u l t s a n d W a r n i n g s

Code

Message

Warning description

Possible problem and solution(s)

11

Inv. Under Voltage

Under voltage on the inverter

side

Problem

• The inverter voltage is too low

Solution(s)

• Check the inverter voltage

• Check the inverter parameter

• Check the MC21

12

Inv. Over Frequency

Over frequency on the inverter

side

Problem

• The grid frequency is outside the permit-
ted range

Solution(s)

• Check the grid frequency

13

Inv. Under Frequency

Under frequency on the inverter

side

Problem

• The grid frequency is outside the permit-
ted range

Solution(s)

• Check the grid frequency

14

Inv. Over Current

Over current on the inverter side Problem

• Short circuit in the IGBT

• Short circuit in the Grid

Solution(s)

• Check the grid connection

• Check the inverter connection

15

MC21 Failure

Inverter AC side contactor failure Problem

• MC21 contactor is open

• Auxiliary switch is inoperable

Solution(s)

• Check the wiring connection

• Change the MC21

16

Inv. Phase Order

Phase order failure on the
inverter side

Problem

• Phase order failure on the inverter

• Wrong phase rotation

Solution(s)

• Check the wiring connection

• Reverse two phases

18

Inductor or TR Over
Temp

Inductor or transformer tempera-
ture is above 150°C

Problem

• Cabinet fan failure

Solution(s)

• Cleaning the fi lters

• Change the cabinet Fan

Table 8: Faults