3 grid parameters – KACO Powador XP100-HV User Manual

Page 53

Advertising
background image

Operating Instructions Powador XP100-HV

Page 53

P a r a m e t e r

P a r a m e t e r

8.3 Grid

Parameters

Parameters

Units

Ranges

Descriptions

Default

Rated Grid Voltage

V

208 ~ 400

Rated value of the grid voltage

380

Rated Grid Fre-
quency

Hz

50 ~ 60

Rated value of the grid frequency

60

Grid Over Voltage
Level 1

%

105 ~ 125

Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 1

110

Grid Under Voltage
Level 1

%

75 ~ 110

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 1

90

Grid Over Frequency
Level 1

Hz

0.0 ~ 3.0

Upper limit for grid over frequency level 1

0.2

Grid Under Fre-
quency Level 1

Hz

0.0 ~ 3.0

Lower limit for grid under frequency level 1

2

Frequency Depend-
ant Power Reduction
Enable

N/A

On(1), Off (0)

“On” Represents what the frequency dependant
power reduction is working

0

Power Gradient
Mode

N/A

0 ~ 3

This parameter determines when “Power Gradient”
is activated.

0 : Disable

1: Activated when connected to grid after fault
(Medium Voltage Requirements)

2: Activated according to VDE-AR-N 4105 (Low
Voltage Requirements)

3: Activated whenever connected to grid (TERNA
Grid Code)

0

Power Gradient
Ramp

sec

0.0 ~ 600

Time for power gradient ramp

600

Time shift

sec

0.0 ~ 6000

Delay time for inverter start

0

Gate-way Enable

N/A

0.0 ~ 1.0

Reserved parameter

0

Grid Level 2 Protec-
tion Enable

N/A

On(1), Off (0)

“On” represents what grid level 2 protection is
working

1

Grid Over Voltage
Level 2

%

105 ~ 130

Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2

120

Grid Under Voltage
Level 2

%

75 ~ 100

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2

80

Grid Under Fre-
quency Level 2

Hz

0.0 ~ 3.0

Lower limit for grid under frequency level 2

2.5

Grid Over Voltage
Level 1 Trip time

ms

1000 ~ 10000

Time for grid over voltage level 1 trip

5000

Table 12: Grid Parameters