3 unit description, 1 technical data – KACO Powador XP100-HV User Manual

Page 8

Advertising
background image

Page 8

Operating Instructions Powador XP100-HV

U n i t D e s c r i p t i o n

3 Unit

Description

3.1 Technical

Data

Electrical Data

Input levels

Max. PV generator power

110 kW

MPPT range

450 to 830 V

No-load voltage

A maximum of 1000 V

Voltage/current ripple

< 3 % / < 4 %

Max. input current

245 A

Overvoltage protection

SPD

Output levels

Rated power

100 kW

Max. power

100 kW

Line voltage

In accordance with country-specifi c guidelines

Output voltage

3*380 / 400 V (±10%)

Rated current

153 A

Max. current

153 A

Rated frequency

50 / 60 Hz

cos phi

≥ 0.99 at rated power

Distortion factor

< 3 % at rated power

Fault signal relay

Potential-free NO contact, max. 30 V/1 A

S0 output

Open collector output, max. 30 V/50 mA

General electrical data

Max. effi

ciency

97.10 %

European effi

ciency

96.50 %

Standby

< 100 W

Grid monitoring

Compliant with VDEW guidelines

Table 1: Electrical data of the inverter