2 inverter parameters – KACO Powador XP100-HV User Manual

Page 52

Advertising
background image

Page 52

Operating Instructions Powador XP100-HV

P a r a m e t e r

P a r a m e t e r

Parameters

Units

Ranges

Descriptions

Default

DC Over Voltage
Level

V

dc

300 ~ 950

Upper limit for PV over voltage fault

950

DC Over Current
Level

%

0 ~ 150

Upper limit for PV over current fault

130

MPP Factor

N/A

0 ~ 1

Maximum power point factor

0.8

MPP Range Upper

V

dc

10 ~ 300

Upper limit of maximum power point

80

MPP Range Lower

V

dc

10 ~ 300

Lower limit of maximum power point

80

PV Operation Level

V

dc

900 ~ 950

Maximum PV operation level

930

Table 10: PV Array Parameters

8.2 Inverter

Parameters

Parameters

Units

Ranges

Descriptions

Default

Transformer & Type

N/A

0 ~ 4096

This parameter determines device specifi c informa-
tion such as a switch type on DC side and whether
the inverter has an internal transformer.

The setting value is represented by the combination
of bit fi elds as below

0

th

bit: Internal transformer

1

st

bit: Manual CB10

2

st

bit: S Phase Sensor

8

st

~ 11

st

bit: Inverter Type

1

Inverter Capacity

kW

100 ~ 500

Power Capacity of the inverter

100

Inverter Over
Current Level

%

0 ~ 200

Upper limit for inverter over current fault

130

Current Limit

%

0 ~ 150

Limit of current which produces from the inverter

100

Cabinet Temp.
Maximum

°C

30 ~ 70

Maximum cabinet temperature for warning

55

Cabinet Temp.
Minimum

°C

-25 ~ 10

Minimum cabinet temperature for warning

-15

PEBB Temperature
Unbalance Level

°C

5 ~ 30

When temperature diff erence between each PEBB

exceeds this parameter setting, warning will be
raised.

10

Table 11: Inverter Parameters