P a r a m e t e r

P a r a m e t e r

Parameters

Units

Ranges

Descriptions

Default

Grid Over Voltage
Level 2 Trip time

ms

40 ~ 2000

Time for grid over voltage level 2 trip

100

Grid Under Voltage
Level 1 Trip time

ms

1000 ~ 10000

Time for grid under voltage level 1 trip

5000

Grid Under Voltage
Level 2 Trip time

ms

40 ~ 2000

Time for grid under voltage level 2 trip

100

Grid Under Fre-
quency Level 1 Trip
time

ms

1000 ~ 20000

Time for grid under frequency level 1 trip

10000

Grid Under Fre-
quency Level 2 Trip
time

ms

40 ~ 2000

Time for grid under frequency level 2 trip

100

Grid Over Frequency
Level 1 Trip time

ms

40 ~ 2000

Time for grid over frequency level 1 trip

100

FRT Enable

N/A

On(1), Off (0)

“On” represents what FRT is working

0

Grid Over Voltage
FRT Enable

N/A

On(1), Off (0)

“On” represents what the grid overvoltage FRT is
working

0

Power Reduction
Gradient Level

%/Hz

0.0 ~ 100

Gradient level for frequency dependant power
reduction

40

Power Reduction
Deactivation
Frequency

Hz

0.0 ~ 0.3

Frequency limit for power reduction deactivation

0.05

Grid Over Frequency
Level 2

Hz

0.0 ~ 3.0

Upper limit for grid over frequency level 2

1.5

Grid Over Frequency
Level 2 Trip time

ms

40 ~ 2000

Time for grid over frequency Level 2 trip

100

Reconnection
Condition Mode

N/A

0 ~ 2

This parameter determines when “Reconnection
condition” will be checked.

0: Disable

1: Checked before connected to grid (Medium
Voltage Requirements)

2: Checked according to VDE-AR-N 4105 (Low
Voltage Requirements)

1

Reconnection
Condition Upper
Voltage

%

-1 ~ 130

This parameter represents the upper voltage in the
range of “Reconnection condition” as a percentage
of the rated value.

The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

-1

Table 12: Grid Parameters