6 grid over voltage level slow – KACO Powador XP100-HV User Manual

Page 62

Advertising
background image

Page 62

Operating Instructions Powador XP100-HV

P a r a m e t e r

Power Gradient Mode

MANUAL
(Manual Operation)

NORMAL
(Normally discon-
nected from grid)

FAULT
(Disconnected from
grid due to fault)

0 (Disable)

Deactivated

Deactivated

Deactivated

1 (Activate after fault)

Deactivated

Deactivated

Activated

2 (VDE-AR-N 4105)

Deactivated

Deactivated

Activated

3 (TERNA)

Activated

Activated

Activated

Reconnection Condi-
tion Mode

MANUAL
(Manual Operation)

NORMAL
(Normally discon-
nected from grid)

FAULT
(Disconnected from
grid due to fault)

0 (Disable)

Deactivated

Deactivated

Deactivated

1 (Activate always)

Activated

Activated

Activated*

2 (VDE-AR-N 4105)

Deactivated

Activated

Activated*

* When inverter is disconnected from grid due to fault, system checks “Reconnection Condition” for the time set-
ting of {Reconnection Condition Check Time After Fault} parameter. In other cases, system checks the “Reconnec-
tion Condition” for the time setting of {Reconnection Condition Check Time Normal}.

8.3.6 Grid Over Voltage Level Slow

Figure 53: Grid Over Voltage Level Slow