Operating Instructions Powador XP100-HV

Page 51

P a r a m e t e r

P a r a m e t e r

8 Parameter

The KACO XP100-HV parameters are pre-confi gured for operation. These parameters make KACO XP series invert-
ers to be powerful, effi

cient and perfectly suited for implementing large-scale PV plants.

The KACO XP100-HV parameters are subdivided into ten:

PV

Array

Setting values for MPPT control and startup of inverter

Inverter

Setting values for inverter rate and cabinet temperature

Grid

Setting values for abnormal and rated levels of grid

Time

Setting values for the current time

Digital

Setting values for digital interface

Analog

Setting values for analog interface

Controller

Setting values for inverter control

Trace

Setting values for inverter fault analysis

Off set

Setting values for sensing off set calibration

Gain

Setting values for sensing gain calibration

8.1

PV Array Parameters

Parameters

Units

Ranges

Descriptions

Default

MPPT Enable

N/A

On(1), Off (0)

“On” represents what MPPT is operating

1

MPPT V Maximum

V

dc

0 ~ 900

Maximum voltage to run MPPT

830

MPPT V Start

V

dc

450 ~ 800

MPPT wake-up voltage

600

MPPT T Start

sec

0 ~ 600

Time delay for MPPT wake-up

300

MPPT P Stop

W

0 ~ 10000

Disconnect inverter from Grid when PV output

power is lower than the setting value of {MPPT P
Stop}.

1000

MPPT T Stop

sec

0 ~ 600

Time delay while inverter decides if PV output

power is lower than the setting value of {MPPT P
Stop}.

30

MPPT V Minimum

V

dc

200 ~ 800

Minimum voltage to run MPPT

410

Table 10: PV Array Parameters