2 frt enable on – KACO Powador XP100-HV User Manual

Page 58

Advertising
background image

Page 58

Operating Instructions Powador XP100-HV

P a r a m e t e r

8.3.2

FRT Enable On

The parameter when FRT Enable is on is as follow.

Parameters

Units

Ranges

Descriptions

Default

FRT Enable

N/A

On (1), Off (0)

“On” represents what FRT is operating

1

Grid Under Voltage
Level 2

%

75 ~ 100

Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage level 2

15

Grid Under Voltage
Level 1 Trip time

ms

1000 ~ 10000

Time for grid under voltage Level 1 trip

2000

Grid Under Voltage
Level 2 Trip time

ms

40 ~ 2000

Time for grid under voltage Level 2 trip

150

MPP Range Upper

V

dc

10 ~ 300

Upper limit of maximum power point

300

MPP Range Lower

V

dc

10 ~ 300

Lower limit of maximum power point

300

Table 13: FRT Enable On

Grid Under Voltage

Figure 49: Grid under voltage

1.

U > 1.1*U

rated

, t > 2s  Grid Over Voltage Level 1 Fault

2. U > 1.2*U

rated

, t > 150ms  Grid Over Voltage Level 2 Fault