Operating Instructions Powador XP100-HV

P a r a m e t e r

Parameters

Units

Ranges

Descriptions

Default

Cabinet FAN PWM

-

0 ~ 100

Reserved parameter

100

Remote Power
Control Ramp

sec

0 ~ 600

The slope of inverter output active poser when
remote power is controlled

10

Total Yield

kWh

0 ~ 99999999

Check total yield of generation (Read only)

-

Today Yield

kWh

0 ~ 99999999

Check day yield of generation (Read only)

-

IIVCD P Gain

-

0 ~ 99999

Inverter output voltage controller’s D-axis P gain
for Initial operation voltage

0.6

IIVCD I Gain

-

0 ~ 99999

Inverter output voltage controller’s D-axis I gain for
initial operation voltage

1.5

IIVCQ P Gain

-

0 ~ 99999

Inverter output voltage controller’s Q-axis P gain
for initial operation voltage

2

IIVCQ I Gain

-

0 ~ 99999

Inverter output voltage controller’s Q-axis I gain for
Initial operation voltage

5

Anti-Islanding
Enable

-

0 ~ 99999

The use of anti-islanding controller, Yes(1) NO(0)

0

APS Line Deadband -

0 ~ 99999

The setup value for anti-islanding control

0.11

Reactive Power Limit -

0 ~ 99999

The setup value for anti-islanding control

0.06

Wind Speed

-

0 ~ 99999

Reserved parameter

-

Power Derating
Enable

-

0 ~ 1

The use of power decline controller according to
PEBB temperature, Yes(1) NO(0)

0

Power Derating
Enable Temperature

-

50 ~ 100

Temperature level which starts decreasing power
according to PEBB temperature

80

Power Derating
Disable Temperature

-

40 ~ 90

Temperature level which stops decreasing power
according to PEBB temperature

60

Power Derating
Reference Tempera-
ture

-

45 ~ 95

PEBB temperature reference value

70

Power Derating P
Gain

-

0 ~ 10

Power declining controller’s P gain according to
PEBB temperature

2

Grid IIR Filter Cutoff
Frequency

Hz

0 ~ 10

Filter cutoff frequency used for RMS value detec-
tion of grid voltage

1.5

Asynchronous Fault
Count

-

0 ~ 100

Reserved parameter

10

Asynchronous Fault
Enable

-

0 ~ 1

Reserved parameter

0

Grid Positive
Sequence

0

999.9

Positive sequence value of grid

-

Table 17: Controller Parameters