2 faults – KACO Powador XP100-HV User Manual

Page 41

Advertising
background image

Operating Instructions Powador XP100-HV

Page 41

F a u l t s a n d W a r n i n g s

6.2 Faults

Code

Message

Description

01

PV Over Voltage

PV voltage exceeds the parameter [DC over voltage Level]

02

PV Over Current

PV current exceeds the parameter [DC over current Level]

03

PV Under Voltage

Voltage of the DC input is below the minimum running voltage

04

CB10 (PV Contactor) Failure

PV side contactor (CB10) failure

05

PV Polarity Failure

Polarity (+, -) of PV side is reversed

06

Ground Fault

PV side ground fault

10

Inv. Over Voltage

Over voltage on the inverter side

11

Inv. Under Voltage

Under voltage on the inverter side

12

Inv. Over Frequency

Over frequency on the inverter side

13

Inv. Under Frequency

Under frequency on the inverter side

14

Inv. Over Current

Over current on the inverter side

15

MC21 (Inv. MC) Failure

Inverter side contactor (MC21) failure

16

Inv. Phase Order

Phase order failure on the inverter side, wrong phase rotation

18

Inductor or TR Over Temp.

Inductor or Transformer temperature is above 150°C

20

PEBB 1 IGBT Fault

PEBB 1 IGBT failure

21

PEBB 2 IGBT Fault

PEBB 2 IGBT failure

22

PEBB 3 IGBT Fault

PEBB 3 IGBT failure

24

PEBB Over Temp. Analog

The temperature of the heat-sink exceeds 90°C (194°F)

25

PEBB Over Temp. Digital

The heat-sink temperature generated by the thermal trip device has

exceeded operational parameters (Thermal Switch)

30

Grid Over Voltage Level 1

Over voltage Level 1 on the grid side

31

Grid Under Voltage Level 1

Under voltage Level 1 on the grid side

32

Grid Over Frequency Level 1 Over frequency Level 1 on the grid side

33

Grid Under Frequency
Level 1

Under frequency Level 1 on the grid side

34

CB20 (Grid SW) Trip

CB20 (AC Disconnect/Grid circuit breaker) was tripped during operation

35

Grid Over Voltage Level 2

Over voltage Level 2 on the grid side

36

Grid Under Voltage Level 2

Under voltage Level 2 on the grid side

37

Grid Under Frequency
Level 2

Under frequency Level 2 on the grid side

38

Grid Over Frequency Level 2 Over frequency Level2 on the grid side

40

Parameters Version Error

Diff erent version between the NVSRAM parameter table and the pro-

gram parameter table

41

Flash Memory Failure

C6000 DSP program fl ash memory failure in XCU (main control) board