3 error code – KACO Powador XP100-HV User Manual

Page 42

Advertising
background image

Page 42

Operating Instructions Powador XP100-HV

F a u l t s a n d W a r n i n g s

F a u l t s a n d W a r n i n g s

Code

Message

Description

42

FPGA Failure

FPGA failure in XCU (main control) board

43

DSP28x Failure

F2000 DSP failure in XCU (main control) board

44

ADC Failure

ADC block failure in XCU (main control) board

45

NVSRAM Failure

NVSRAM Failure in XCU (main control) board or invalid parameter setting

46

Asynchronous

Synchronous fail of Grid and Inverter

50

Emergency Stop

A door is open

51

Cabinet Over Temp.

Temperature of cabinet is too high. Inverter has stopped operation

Table 6: Faults

6.3 Error

code

The Inverter can detect faults during operation. The inverter will display the fault in the GUI. Faults are indicated
in the GUI with an error code, and a plain text message with the error code and system plant name in the text
line will be sent to the system operator (only available if purchased and confi gured during setup). This section
describes how to recognize the types of faults and how to correct these faults.

Warnings

Code

Message

Warning description Possible

causes/Diagnosis

81

SP1 (PV SP) Failure

Failure of the PV side surge pro-

tector (SP1)

Problem

• Lightning strike on or near the PV system
wiring

Solution(s)

• Visual inspection

• Change the SPD

83

PV Fuse Failure

PV side Fuse failure (option)

Problem

• PV system wiring short

• Short circuit in the IGBT

Solution(s)

• Check the input current

• Check module wiring

• Change the FUSE

100

PEBB Over Temp.
Warning

The temperature of the heat-sink
of the PEBB exceeds 75°C (167°F)

Problem

• PEBB Fan Failure

Solution(s)

• Clean the fi lters or PEBB heat-sink fi ns

• Change the PEBB Fan

Table 7: Warnings