F a u l t s a n d W a r n i n g s

F a u l t s a n d W a r n i n g s

Code

Message

Warning description Possible

causes/Diagnosis

101

PEBB Fan Failure

PEBB heat-sink fan failure

Problem

• PEBB Fan Failure

Solution(s)

• Change the PEBB Fan

110

SP2 (Grid SP) Failure

Failure of the grid side surge pro-
tector (SP2)

Problem

• Lightning strike on or near the grid

system wiring

Solution(s)

• Visual inspection

• Change the SPD

120

Test Mode

The system is working in test

mode

Problem

• The system is working in test mode

Solution(s)

• Change the parameters in the GUI

130

Cabinet Over Temp.
Warning

The temperature of the cabinet

exceeds operational parameters

Problem

• Cabinet Fan Failure

Solution(s)

• Clean the air fi lters

• Change the cabinet fan

131

Cabinet Under Temp.
Warning

The temperature of the cabinet

falls below operational parame-
ters

Problem

• Ambient temperature is too low for oper-
ation

134

Control SMPS Failure

Failure of the control SMPS

Possible causes

• Failure of the control SMPS

Solution(s)

• Change the control SMPS

Table 7: Warnings