KACO Powador XP100-HV User Manual

Page 55

Advertising
background image

Operating Instructions Powador XP100-HV

Page 55

P a r a m e t e r

P a r a m e t e r

Parameters

Units

Ranges

Descriptions

Default

Reconnection
Condition Lower
Voltage

%

-1 ~ 100

This parameter determines the lower voltage of
“Reconnection condition” range as a percentage of
the rated value.

The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

95

Reconnection
Condition Upper
Frequency

Hz

-1 ~ 3

This parameter determines the upper frequency of
“Reconnection condition” range as an increment
from the rated value.

The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

0.05

Reconnection
Condition Lower
Frequency

Hz

-1 ~ 3

This parameter determines the lower frequency of
“Reconnection condition” range as a decrement
from the rated value.

The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

2.5

Reconnection
Condition Check
Time Normal

sec

0 ~ 1800

This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.

5

Reconnection
Condition Check
Time After Fault

sec

0 ~ 1800

This parameter is used for time check during
“Reconnection condition” for after fault only.

5

Grid Over Frequency
Level 3

Hz

0 ~ 3

Upper limit for grid over frequency level 3

2

Grid Over Frequency
Level 3 Trip Time

ms

40 ~ 2000

Time for grid over frequency Level 3 trip

100

Grid Over Voltage
Level Slow

%

105 ~ 115

This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.

If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.

(Low Voltage Requirements)

110

Grid Over Voltage
Level Slow Shift
Average Time

sec

-1 ~ 3000

This parameter determines how long the average
RMS value of grid voltage will be calculated.

(Low Voltage Requirements: 600 seconds duration)

Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.

-1

Reconnection
Condition Warning
Delay

sec

0 ~ 600

Time delay for Reconnection Condition Warning

10

Table 12: Grid Parameters