4 power gradient enable on – KACO Powador XP100-HV User Manual

Page 60

Advertising
background image

Page 60

Operating Instructions Powador XP100-HV

P a r a m e t e r

1.

It disables Grid Over Frequency Level 1 Fault.

2. f < f

rated

+ 1.5Hz, t > 100ms*  Grid Over Frequency Level 2 Fault and Grid Over Frequency Level 3 Fault

*The setting values for Grid Over Frequency Level 2 and Grid Over Frequency Level 3 can be diff erent with
each other according to the requirements (Default is same).

8.3.4 Power Gradient Enable On

Figure 51: Power Gradient Enable On

This function is for PV inverter re-generation. Inverter need to generate active power slowly with specifi c slope
when its operation stops due to various reasons. In this case, active power supply cannot be over 10 % of rated
active power per minute.

Advertising