6faults and warnings, 1 warnings – KACO Powador XP100-HV User Manual

Page 40

Advertising
background image

Page 40

Operating Instructions Powador XP100-HV

F a u l t s a n d W a r n i n g s

6

Faults and Warnings

When a problem occurs in the system, the Inverter will beep and inform the user on the GUI. The Inverter displays
two basic error messages. The fi rst, the fault, is a serious problem that causes the inverter to stop running. The
second, a warning, is a minor problem that does not cease the system operation. The GUI will indicate faults in red
and warnings in yellow. The user can fi nd a description of the diff erent fault and warnings in the following Tables.

6.1 Warnings

Code

Message

Description

81

SP1 (PV SP) Failure

Failure of the PV side surge protector (SP1)

82

CB10 (PV Contactor) Failure

PV side contactor (CB10) failure

83

PV Fuse Failure

PV side Fuse failure (option)

84

Ground Fault Warning

The insulation resistance of the PV falls short of the limit set in the ground
fault monitoring for Alert1 (option)

85

PV Over Voltage

PV voltage exceeds the parameter [DC over voltage Level]

100

PEBB Over Temp. Warning

The temperature of the PEBB (Power Electronics Building Block) heatsink
exceeds 75°C (167°C)

101

PEBB Fan Failure

Failure of a PEBB (Power Electronics Building Block) fan

110

SP2 (Grid SP) Failure

Failure of the grid side surge protector (SP2)

120

Test Mode

The system is working in test mode

121

Watchdog

Abnormalities detection in the DSP

125

Parameter Invalid

Parameter is invalid value

130

Cabinet Over Temp.
Warning

The temperature of the cabinet exceeds the operational parameter [Cab-
inet Temperature Maximum]

131

Cabinet Under Temp.
Warning

The temperature of the cabinet falls below the operational parameter

[Cabinet Temperature Minimum]

134

Control SMPS Failure

Failure of the control SMPS (Switching Mode Power Supply)

Table 5: Warnings