This function abides by “Low Voltage Requirements” of Germany and raises a fault for “Grid Over Voltage Level
Slow” when the average RMS value for grid voltage exceeds the setting value of this parameter. The upper limit
for the average of grid voltage where the fault will be raised and the duration for calculation of the average
value are possible to adjust with the parameter. According to “Low Voltage Requirements”, they are 110 % and
600 seconds respectively.

In the picture above, although the RMS value of the grid voltage exceeds the setting of “Grid Over Voltage Level
Slow”, a fault will not be raised. Because the average value for last 10 minutes does not exceed the setting value.
A fault is raised only when the average RMS value of grid exceeds the setting of the parameter which is “Grid
Over Voltage Level Slow”.

8.4 Time

Parameters

Parameters

Units

Ranges

Descriptions

Default

Year

N/A

2000 ~ 3000

The present year

-

Month

N/A

1 ~ 12

The present month

-

Day

N/A

1 ~ 31

The present date

-

Time

N/A

0 ~ 23

The present hour

-

Minute

N/A

0 ~ 59

The present minute

-

Second

N/A

0 ~ 59

The present second

-

Table 14: Time Parameters

8.5 Digital

Parameters

Parameters

Units

Ranges

Descriptions

Default

DI1 Select

N/A

0 ~ 20

DI1 (Digital Input) selection

0: Disable DI1

1: Reserved for later use

2: Reserved for later use

3: Start/Stop operation of the inverter with DI1 (DI1
Recognition pattern: 1sec – Stop, 2sec – Start)

3: Start/Stop operation of the inverter with DI1 (DI1
Recognition pattern: 200msec – Stop, 400msec –
Start)

0

DO1 Select

N/A

0 ~ 20

DO1 (Digital output) selection

0: DO1 signal will be sent at fault state

0

RPC Mode Select

N/A

0 ~ 2

The remote power control function of XP series
inverter. Cos-phi control operates when this
parameter is 2

0: Disable

1: Master

2: Slave (for Cos-phi control operation)

2

Table 15: Digital Parameters