Emerson E2 User Manual

Page 102

Advertising
background image

9-8

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Point Name The Point Name is simply a name for

the point that may be used as a reference.

Assigning a descriptive name to a point makes setting

up inputs for applications much easier. For example,
if you have an inside temperature sensor located in
Zone 1 of your building, you may name it “ZONE 1
TEMP”. Then, when programming your HVAC
applications, you may easily define Zone 1’s temper-
ature sensor input by tying it to ZONE 1 TEMP. This
keeps you from having to keep track of which sen-
sors are tied to which point numbers.

You are required to enter a point name in the Point
Name
field. The default name is “:{BOARD
NAME}:{BOARD NUMBER}:{POINT NUM-
BER}.”

Board/Point # The Board/Point number will auto-

matically be defined if you are configuring the point from
the Input Status screen.

Sensor Type The analog input may come from a

number of different sensor types.

Select Eng. Units The engineering units of the

Figure 9-6

- Analog Input Screen

Sensor Type

Description

Temperature

CPC Standard Temp Sensor

12V-100 LB

12VDC 100 PSI transducer
(1-6VDC output) (Discontin-
ued)

12V-200 LB

12VDC 200 PSI transducer
(1-6VDC output) (Discontin-
ued)

Table 9-2

- Sensor Input Types

12V-500 LB

12VDC 500 PSI transducer
(1-6VDC output) (Discontin-
ued)

5V-100 LB

5VDC 100 PSI transducer
(0.5-4.5VDC output)

5V-200 LB

5VDC 200 PSI transducer
(0.5-4.5VDC output)

5V-500 LB

5VDC 500 PSI transducer
(0.5-4.5VDC output)

Refrig. Leak

Refrigerant Leak Detector
(not IRLDS)

Refrig. Level

Refrigerant Liquid Level
Probe

Liquid Level

Liquid Level Float Sensor

Light Level

Light Level Sensor

Linear

General purpose linear out-
put sensor

Humidity

Relative Humidity sensor

Pulse Accum.

Kilowatt value from KW
transducer pulse accumula-
tion readings (see Units Per
Pulse
on

page 9-9

)

KW Transducer

Kilowatt transducer using 4-
20ma/0-5V signal

Dewpoint

Dewpoint probe

LM235 Temp

Linear voltage output tem-
perature sensor

PT2 Temp

Danfoss PT2 temperature
sensor

CDK Temp

CDK 2097MC temperature
sensor

20K Pot Adjust

Standard temperature sensor
with offset adjustment
(potentiometer)

ATP Hi Temperature

CPC’s 100K High Tempera-
ture Sensor (Range 0 - 500
DegF)

86K Temp

Copeland’s integral dis-
charge temperature sensor

Sensor Type

Description

Table 9-2

- Sensor Input Types