Echelon Network Problems

Faulty wiring.

Check connections. Are wires
broken or loose? Check network
polarity (positive to positive/
negative to negative). Check for
wire damage.

Termination jumpers are set
incorrectly.

Check for proper setting of ter-
minating resistance jumpers.
Network segment should be ter-
minated on the two endpoints of
the daisy chain and unterminated
everywhere else. Refer to Sec-
tion 8.4,
Device Termination.

Subnet (unit #) is set incorrectly.

Each controller must have its
own subnet address. Refer to
Section 8.3, Echelon Network
Structuring (Daisy-Chains)
.

SYMPTOM

POSSIBLE PROBLEM

SOLUTION