11 set up network baud rates, 1 com1 serial (rs232) baud rate, 2 i/o network baud rate – Emerson E2 User Manual

Page 124: 11 s, Etwork, Ates

Advertising
background image

10-12

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

10.11 Set Up Network Baud
Rates

10.11.1 COM1 Serial (RS232) Baud
Rate

To access COM1 Serial (RS232) and I/O Network

baud rates:

1.

Press

to open the Main Menu

2.

Press

(System Configuration)

3.

Press

(System Information)

4.

Press

(General Controller Info) aand navigate

to the COM1 Baud rate field

The COM1 Baud rate field determines the speed of

communications between the E2 and an RS232 device
(such as a satellite link or PC).

The baud rate selected in this field should correspond

with the baud rate for the RS232 device. For example, if
connecting a PC to this port, the PC’s COM port should
be set up to communicate at the same rate as what is set
in this field.

There are multiple options to choose from. Select one

of the options below using

 (LOOK UP) depending

on the type of connection.

1200 Baud (devices that operate at 1200)

2400 Baud (devices that operate at 2400)

4800 Baud (devices that operate at 4800)

• 9600 Baud (recommended for satellite)

• 19.2 Kbaud (recommended for modem)

• 38.4 Kbaud (recommended for modem)

• 57.6 Kbaud (recommended for modem)

• 115.2 Kbaud (recommended for direct connect)

10.11.2 I/O Network Baud Rate

When a comport is set to I/O Net, the I/O Network

baud rate is the rate at which the E2 will communicate
with input and output boards on the RS485 I/O Network,
and is located directly below the RS232 Baud rate field.

Press

 to select the baud rate. The appropriate

baud rate is 9600 baud.

NOTE: If a baud rate is the controller must be
rebooted (turned OFF then ON again) to make
the baud rate change occur.

Figure 10-18

- COM1 Baud Rate Setup (Serial RS232)

Figure 10-19

- I/O Network Baud Rate Setup