Appendix C: Alarm Advisory Messages

C

-

3

Comb Temp Hi Limit Exceeded

User

The combined temperature of an entire Standard Cir-
cuit or Case Control Circuit has risen above its pro-
grammed high temperature setpoint.

Comb Temp Low Limit Exceeded

User

The combined temperature of an entire Standard Cir-
cuit or Case Control Circuit has fallen below its pro-
grammed low temperature setpoint.

Commission failed-chk network

50

Commission of Echelon controller failed; binding of
NV was not successful. Check the Echelon network.

Communication Port 1 Is Down

20

E2 cannot communicate with the RS232 port on the
E2 main board. The E2 main board likely needs
repair or replacement.

Communication Port 2 Is Down

20

E2 cannot communicate with the RS485 network port
on the E2 main board. The E2 main board likely
needs repair or replacement.

Communication Port 3 Is Down

20

E2 cannot communicate with the modem slot on the
E2. The E2 main board likely needs repair or replace-
ment.

Communication Port 4 Is Down

20

COM4 is used by service personnel to attach hard-
ware used in test or debug functions. This alarm indi-
cates the port that allows E2 to communicate with
these devices is faulty. The E2 board likely needs
repair or replacement.

Communication Port 6 is down

20

E2 cannot communicate with port 6 on the E2 main
board.

Completed Firmware Update

50

The E2’s firmware was successfully updated.

Config Loss - Chg In Tmpl Rev.

15

Due to a difference between configuration templates
in a previous E2 version and templates in the current
version, configuration data could not be restored.

Config Loss-CRC Error

15

Due to an internal error, E2 has lost configuration
data.

Config Loss-File CRC Error

15

Due to an internal error, E2 has lost configuration
data.

Config Not Saved To Flash

20

E2 could not save configuration data to flash mem-
ory.

Controller (or Device) Absent From
Network

20

The current E2 could not find the specified E2, I/O
board, or Echelon controller

Controller Reset

50

An ARTC/MultiFlex RTU has gone through a reset.

Controller Shutdown

50

The E2 has gone through a shutdown.

Controller Startup

50

The E2 has re-started after a shutdown.

Alarm Name

Default

Priority

Definition