Appendix F: Troubleshooting

F

-

1

Appendix F: Troubleshooting

The chart below describes symptoms and solutions if troubleshooting the system or equipment is needed. For further

information, contact Retail Solutions Service at 1-800-829-2724.

SYMPTOM

POSSIBLE PROBLEM

SOLUTION

I/O Network Problems

I/O board not getting power.

Check I/O board power--is the
green STATUS light on? If not,
check power wiring connections,
and use a multimeter to verify
the board is getting 24VAC.
Reset power to board.

I/O board not communicating or
won’t come online.

Check I/O network connections:
1. Check wire polarity (positive
to positive/negative to negative)
2. Check for broken or loose
wires.

Dip switches are set incorrectly.

Check I/O board network dip
switches. Verify network ID
number is not a duplicate and
that baud rate switches are set to
9600. (If switches are wrong,
make changes and then reset the
controller.) Refer to Section
6.1.6,
Network ID Numbers
(Board Numbers)
.

Terminating resistance jumpers
are set incorrectly.

Check for proper setting of ter-
minating resistance jumpers.
Network segment should be ter-
minated on the two endpoints of
the daisy chain and unterminated
everywhere else. Refer to Sec-
tion 6.1.8,
Setting the Terminat-
ing and Biasing Jumpers
.

Boards are not powered.

Check Network/Power voltages.
Refer to Section 6.1.9, Powering
the I/O Boards
.