6-18

E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

32

2

5

3

4

1

1. Connect 16A1 to the RS485 I/O Network.

2. Set the network address on the first five
rockers of dip switch S3.

3. Set the network baud rate using rockers 6
and 7 of dip switch S3.

4. Set RS485 termination jumpers UP (term) if
at either end of a daisy chain. Otherwise, set
jumpers DOWN (not term).

Note: If you change any dip switch settings
while the board is powered, disconnect the
power and re-power the board to reset.

5. Connect board to the 24VAC

secondary of the power transformer.

center-tapped

TO

OTH

ER

RS4

85

DEV

ICES

TO

OTHE

R

RS48

5

DEVIC

ES

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

1

ON

2

2

3

3

4

4

5

5

6

6

7

7

8

8

1

1

ON

BOARD 1

BOARD 2

BOARD 3

BOARD 4

BOARD 5

BOARD 6

BOARD 7

BOARD 8

BOARD 9

BOARD 10

BOARD 11

BOARD 12

BOARD 13

BOARD 14

BOARD 15

BOARD 16

ADDRESS

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

7

7

7

8

8

8

1

1

1

BAUD RATE

9600 baud

19200 baud

16AI INSTALLATION GUIDE

DAISY CHAIN CONFIGURATION

SET TERMINATING JUMPERS:

UP

DOWN

DOWN

UP

JU1 JU2 JU3

JU1 JU2 JU3

UP

DOWN

1

WIRING FOR 640-0056, 56VA Transformer,

and 640-0080, 80VA Transformer

PRIMARY SIDE

240

208

C

120

(N

E

U

T

R

A

L

)

(H

O

T

)

120/208/240 VAC

SECONDARY SIDE

24V CT 24V

AC

1

0V

AC

2

AC1

AC2

24VAC Center-Tapped Transformer

24VAC Center-Tapped

L2

L1

Three-conductor non-shielded cables
are the recommended wire
for connecting between the
center-tapped transformer
and I/O boards.

Power Wiring Types:
14 AWG Belden 9495
18 AWG Belden 9493

Earth ground the
0V (center-tapped)
terminal of each board

0V

2

3

4

5

SHIELDED TWISTED PAIR
BELDEN #8761. FOR PLENUM,
USE BELDEN #82761 OR #88761
OR EQUIV.

WIRE + to + (same color)
WIRE 0V to 0V
WIRE - to - (same color)

(Terminated)

(Not Terminated)