ECT MODBUS

The RS485 Network and Hardware Setup

6

-

17

WIRE + to + (same color)
WIRE 0V to 0V
WIRE - to - (same color)

SHIELDED TWISTED PAIR
BELDEN #8761. FOR PLENUM,
USE BELDEN #82761 OR #88761
OR EQUIV.

YELLOW

YELLOW

0V

24 VAC

24 VAC

120/208/240 VAC

• P/N 640-0041, 120VAC Primary,
50VA

• P/N 640-0050, 120VAC Primary,
75VA

• P/N 640-0042, 220VAC Primary,
50VA

• P/N 640-0056, Multi-tap
120/208/240VAC Primary, 56VA

• P/N 640-0080, Multi-tap
120/208/240VAC Primary, 80VA

Note: Please refer to transformer
for primary side wiring.

Acceptable Retail Solutions Transformers: