2 condenser control, 1 air cooled condensers, 1 air cooled strategy – Emerson E2 User Manual

Page 145: 2 temperature differential strategy, Ondenser, Ontrol, 1 air cooled condensers -3, Figure 11-1, In table 11-1 and table 11-2, 2 temperature differential strat- egy

Advertising
background image

Condenser Control

Software Overview

11

-

3

11.2 Condenser Control

An E2 RX is capable of controlling air-cooled or evap-

orative condensers. The E2 RX-300 may control a single
condenser, while the RX-400 may control up to two con-
densers.

11.2.1 Air Cooled Condensers

An air-cooled condenser consists of one or more fans

that blow air across a manifold of tubing to cool heated
refrigerant and condense it into a liquid. The E2 controls
condensers by activating or deactivating fans in order to
maintain discharge pressure or temperature at or below a
chosen setpoint.

A Condenser Control application may use either of two

strategies to operate air cooled condensers: an air-cooled
strategy, or a temperature differential (T-D) strategy.

11.2.1.1 Air Cooled Strategy

The air cooled strategy uses a simple PID control loop

that compares a single Control In input to a PID setpoint.
The resulting percentage is used to activate the condenser
fan(s) necessary to bring the input value down below the
setpoint.

Control inputs for air cooled strategies most commonly

come from a pressure transducer mounted on either the
discharge line, the condenser inlet, or the condenser outlet.
However, temperature sensor values will also be accepted.

11.2.1.2 Temperature Differential Strat-

egy

The temperature differential strategy attempts to keep

a minimum amount of difference between the temperature
of the refrigerant and the ambient outside temperature.

This strategy begins by determining the temperature of

the refrigerant coming into the condenser. This can be sup-
plied by either a temperature sensor or pressure transducer
located near the condenser inlet; if it’s a pressure trans-
ducer, its value will automatically be converted to a tem-
perature value based upon the type of refrigerant.

Figure 11-1

- Diagram of a Suction Group

SUCTION
PRESSURE

CO

NDEN

S

E

R

DISCHARGE
PRESSURE

LIQUID RECEIVER

CASE CIRC

UIT

OIL

PRESSURE

CIRCUIT
CASE TEMP
(FOR FLOATING)

LIQUID LINE
SOLENOID

26507005

D

D

D

OIL RESET SWITCHES

Input

Sensor Type

Wiring

Instructions

Suction Pressure

100 lb. Eclipse
transducer

see Table 9-1 on
page 9-3.

Discharge Pres-
sure

500 lb. Eclipse
transducer

see Table 9-1 on
page 9-3

Oil Pressure

200 lb. Eclipse
transducer

see Table 9-1 on
page 9-3

Case Circuit
Temperature

Temperature

see Table 9-1 on
page 9-3

Oil Reset
Switches

Digital

see Table 9-1 on
page 9-3

Table 11-1

- Suction Group Inputs

Output Device

Wire Output

Board Contacts

to:

Set Failsafe Dip

Switch to:

Notes

Compressor

N.C.

N.C. (up)

If you want a compressor to be OFF during network/power loss,
use N.O. failsafes instead.

Unloader

N.C.

N.O. (down)

These fail-safe settings are specifically for unloaders.

Liquid Line Sole-
noid (LLS)

N.C.

N.C. (up)

Keeps solenoid energized during network/power loss.

Electric Defrost

N.O.

N.O. (down)

Keeps contacts de-energized during network/power loss.

Table 11-2

- Suction Group Outputs

Advertising